### Author:

  • loc 1 - dangerous voltage differentials between instruments.  Shields minimize interference from noise by reducing noise emission and noise susceptibility. 6.1 Outline for Grounding and Shielding Design  Step 1: Understand the safety and noise issues for a product.  Step 2: Know the possible mechanisms of energy coupling.  Step 3: Define the necessary grounds and shields.  Reduce the voltage differentials between external conductor surfaces.  Usually the design is – conducted energy, low frequency (less than 1 MHz) and associated with power lines.  Microwave energy is not a shock hazard but it does pose danger and demands especial attention to shielding. Safety Ground  Provides a path for the dangerous leakage currents ioenotes.edu.npand short circuits.  Properly connected safety ground reduces voltage differential between external surfaces.  Safety ground must be a permanent, continuous, low impedance conductor with adequate capacity that runs from the power source to load.  Don’t rely on a metallic conduct to form the conductive path for the safety ground, corrosion and breaks can from open the circuit.  Don’t rely on building steel either because circulating currents can generate large and noisy ground potentials.  A separate dedicated conductor will avoid these problems. things to remember when to develop wiring for powering instruments: Three  Consider the instrument and power mains as an integrated system.  Always draw your ground scheme to understand the possible circuit paths.  Don’t blindly rely on building steel for a ground conductor. 6.2 Noise, Noise (Energy) Coupling Mechanism and Prevention • Noise is unwanted electrical activity coupled from one circuit into another– 3 components: A source, A coupling mechanism, and A receiver . Downloaded Compiled By: Er. Hari Aryal [[email protected]] Reference: K.R. Fowler | 1