### Author:
- loc 1 - dangerous voltage differentials between instruments. Shields minimize interference from noise by reducing noise emission and noise susceptibility. 6.1 Outline for Grounding and Shielding Design Step 1: Understand the safety and noise issues for a product. Step 2: Know the possible mechanisms of energy coupling. Step 3: Define the necessary grounds and shields. Reduce the voltage differentials between external conductor surfaces. Usually the design is – conducted energy, low frequency (less than 1 MHz) and associated with power lines. Microwave energy is not a shock hazard but it does pose danger and demands especial attention to shielding. Safety Ground Provides a path for the dangerous leakage currents ioenotes.edu.npand short circuits. Properly connected safety ground reduces voltage differential between external surfaces. Safety ground must be a permanent, continuous, low impedance conductor with adequate capacity that runs from the power source to load. Don’t rely on a metallic conduct to form the conductive path for the safety ground, corrosion and breaks can from open the circuit. Don’t rely on building steel either because circulating currents can generate large and noisy ground potentials. A separate dedicated conductor will avoid these problems. things to remember when to develop wiring for powering instruments: Three Consider the instrument and power mains as an integrated system. Always draw your ground scheme to understand the possible circuit paths. Don’t blindly rely on building steel for a ground conductor. 6.2 Noise, Noise (Energy) Coupling Mechanism and Prevention • Noise is unwanted electrical activity coupled from one circuit into another– 3 components: A source, A coupling mechanism, and A receiver . Downloaded Compiled By: Er. Hari Aryal [[email protected]] Reference: K.R. Fowler | 1